Detail Aecl AVC-310 Series CO2, Temperature & Humidity Transmitter
Air Quality Monitor
AVC-310 series CO2 transmitter is designed for measuring the ambient carbon dioxide concentration or with optional measurement of temperature & humidity and provide signal output for monitoring or control. Utilizing NDIR sensing element ensures its accuracy of measurement. By controlling the ventilation or air-conditioning system based on actual demand, it helps to reduce energy consumption while maintaining a healthy indoor climate.
Features:
Rapid response time, high stability, high accuracy
Internal sensing element design
Streamline shape and elegant design
Complete product line and multifunction for various applications
Specifications:
Model No. AVC-301 CO2 transmitter
Measurement range: 0~2,000 ppm (Standard) or 0~9999 ppm (High level)
Sensing element: Gold-plated infrared (NDIR) wave-guide technology with Automatic Baseline Correction (ABC) and passive gas diffusion (no moving parts)
Response time: < 10 sec. @ 30 cc/min. flow rate ; < 3 min. diffusion time
Accuracy (at 25℃): 0~2000ppm(± 30ppm ±3% of reading), 2001~9999ppm(± 70ppm ±3% of reading)
Repeatability: ± 20ppm + (±reading * 1%)
Zero Drift: < ± 10ppm/yr. with Automatic Baseline Correction (ABC)
Signal output: DC 4~20mA; DC 0~10 V; RS485 (Modbus RTU)
Model No. AVC-311 CO2 + temperature & humidity transmitter
Measurement range:CO2: 0~2,000 ppm (Standard) or 0~9999 ppm (High level)
Temperature: -10 ~ +50℃
Humidity: 0 ~ 100 %RH
Sensing element:CO2:Gold-plated infrared (NDIR) wave-guide technology with Automatic Baseline Correction (ABC) and passive gas diffusion (no moving parts)
Temperature & humidity: CMOS sensor
Respone time:CO2: <10 sec. @ 30cc/min. flow rate ; <3 min. diffusion time
Temperature: min. 3 sec.;max. 30sec. at τ63%
Humidity: < 8 sec. at τ63%
Accuracy (at 25℃):CO2: 0~2000ppm(± 30ppm ±3% of reading), 2001~9999ppm(± 70ppm ±3% of reading)
Temperature: ±0.3℃
Humidity: ±2 %RH
Repeatability:CO2: ±20ppm + (±reading * 1%)
Temperature: ±0.1℃
Humidity: ±0.1 %RH
Zero Drift:CO2: < ± 10ppm/yr. with Automatic Baseline Correction (ABC)
Temperature: < 0.04 ℃/yr
Humidity: < 0.5 %RH/yr
Signal output: RS485 (Modbus RTU)
General Specifications:
Display range:CO2: 0 ~ 2000 ppm (Standard); 0 ~ 9999 ppm (High level);
Temp.: -9.99 ~ 50.00℃ ; Humidity: 0 ~ 99.9 %RH
Alarm output: Relay output N.O, N.C ( 2A / 30V DC)
Pressure dependence: CO2: 1.6% reading per kPa
Environmental:Temperature: -10 ~ +50℃
Humidity: 0 ~ 95%RH (without condensation)
Storage temperature: -20 ~ +70 ℃.
Warm-up time: ≤ 1 min. (at full specs ≤ 15 minutes)
Power Supply: 12~36 VDC, AC 24V (50/60hz)
Power consumption: <1.7W (peak value)
Installation: Wall mount; Duct-mount
Dimensions(mm)Wall-mount: 113.57(H) x 80(W) x 28.79(D)
Duct-mount: 142.4H x 85W x 47.2D; sensing probe: 130