Detail Aecl AVC-210/510 Series PM 2.5/10 Air Quality Transmitter
Air Quality Monitor
AVC210/ 510 particulate matter sensor / transmitter is applied for indoor air quality monitoring and provides monitoring data as reference for improving air quality. It can accurately measure particulate matter (PM) and send detail data with RS485, Modbus RTU monitoring center or to HVAC system. The immediate action can be to trigger ventilation system or to activate air purifier to ensure better indoor air quality.
Features:
Rapid response time, high stability, high accuracy
Internal sensing element design
Streamline shape and elegant design
Complete product line and multifunction for various applications
Specifications:
Model No. AVC-210 PM2.5 transmitter
Measurement method: Laser scattering method
Measurement range: 0~600μg/m3
Accuracy: 0~ 100μg/m3(±10μg/m3) ; 100~ 600μg/m3 (±10%)
Response time: ≦10 s
Counting efficiency: 98@≧0.5um
Model No. AVC-510 PM10 transmitter
Measurement method: Laser scattering method
Measurement range: 0~600μg/m3
Accuracy: 0~ 100μg/m3(±10μg/m3) ; 100~ 600μg/m3 (±10%)
Response time: ≦10 s
Counting efficiency: 98@≧0.5um
General Specifications:
Display range: 0~600μg/m3
Outputs: RS-485 (Modbus RTU)
Power Supply: DC 12~36V, AC 24V (50/60hz)
Power consumption: 500mA (max)
Installation: Wall mount
Dimensions(mm): 113.57(H) x 80(W) x 28.79(D)
Case material: ABS
IP rating: IP30
Operating environment: -10~50℃(14~122℉) / 0~95%RH, non-condensation
Storage temperature: -10~50℃(14~122℉)